How to activate additional traces

Additional, specific, traces can be generated in the Event Viewer, and hence the Trace.Log file, using the SCADA Basic instruction TRACE.

Use of additional traces can affect PcVue performances and they may cause display and storage of sensitive information. If you enable any of the optional traces, they should be disabled once the issue has been diagnosed and resolved. And you must make sure diagnostics trace files are deleted securely if need be.

For the Variable Manager

Bit 0 Error level 0 Trace( 1, 5, “1”);
Bit 1 Error level 1 Trace( 1, 5, “2”);
Bit 6 Source switch local/external Trace( 1, 5, “40”);
Bit 7 Subscribe/Unsubscribe Trace( 1, 5, “80”);
Bit 8 Recipe Trace( 1, 5, “100”);
Bit 9 Flow regulation, more detail Trace( 1, 5, “200”);
Bit 10 Flow Regulation Trace( 1, 5, “400”);
Bit 16 Subscribe response Trace( 1, 5, “10000”);
Bit 24 Trace writes of variable Trace( 1, 5, “1000000”);

For the LAN Manager

Bit 0 Error level 0 Trace( 1, 3, “1”);
Bit 1 Error level 1 Trace( 1, 3, “2”);
Bit 3 Disconnection and request of connection Trace( 1, 3, “8”);
Bit 4 Watchdog message from client connection Trace( 1, 3, “10”);
Bit 6 Packet size above 64k Trace( 1, 3, “40”);
Bit 7 Flow regulation, Xon/Xoff Trace( 1, 3, “80”);
Bit 8 Send subscribe and regulation Trace( 1, 3, “100”);
Bit 9 Send subscribe, more details Trace( 1, 3, “200”);
Bit 10 Receive subscribe and regulation Trace( 1, 3, “400”);
Bit 11 Distributed bad quality trend counter Trace( 1, 3, “800”);
Bit 12 Sent packet waiting for acknowledgment Trace( 1, 3, “1000”);
Bit 13 Received packet to be acknowledged Trace( 1, 3, “2000”);
Bit 16 Sent packet Trace( 1, 3, “10000”);
Bit 17 Sent packet, more details Trace( 1, 3, “20000”);
Bit 18 Received packet Trace( 1, 3, “40000”)
Bit 19 Received packet, more details Trace( 1, 3, “90000”);
Bit 20 Winsock receive API Trace( 1, 3, “100000”);
Bit 21 WinSock connect Trace( 1, 3, “200000”);
Bit 23 Miscellaneous Trace( 1, 3, “800000”);
Bit 24 Receive Trace( 1, 3, “1000000”);
Bit 26 System variables Trace( 1, 3, “4000000”);
Bit 29 NetBIOS request Trace( 1, 3, “20000000”)

For the Historical Manager

Bit 5 Read trend Trace( 1, 8, “20”);
Bit 6 Read log Trace( 1, 8, “40”);

For the UI Manager

Bit 0 Error level 0 Trace( 1, 6, “1”);
Bit 10 Send subscribe on start-up Trace( 1, 6, “400”);