Test our interfaces !

SCADA/HMI Supervision

SnapVue - Intelligent Digital Assistant

TouchVue - Notifications app. for operations
EmVue - energy monitoring
Download Area
Topic
[KB55]Open Modbus slave protocol with Applicom
Options
Email
Print
| Applies to:
PcVue version 6.10 onwards. |
||
|
|
||
| Summary:
This article explains how to configure an Open Modbus slave protocol with PcVue when Applicom is the Open Modbus Master. |
||
|
|
||
| Details:
With the Applicom card, when you define a new server equipment, it is configured with these parameters:
In the communications configuration menu:
If PcVue acts as an “Open Modbus TCP/IP” server with a Modbus Address of 0, PcVue will not acknowledge requests coming from the Applicom card. Solution Change the slave number in both the Applicom and PcVue configurations to any other value (from 1 to 255). |
||
|
|
||
|