Applies to:
PcVue version 7.10c onwards. |
||
|
||
Summary:
Possibility to temporize the invalidation of variables due to communication failure. |
||
|
||
Details:
The timeout is the period, after the first failure to read the frame to which they are attached, after which the variables are flagged as invalid. Note that an equipment is only flagged as failed after 3 failed attempts to read a frame. That is after the first failure to read a frame plus 2 re-tries at the normal scan rate. Example – a frame is polled at a 1 second rate. The Timeout Before Invalidating Equipment Variables is set to 10 seconds. On failure of the equipment:
Configuration from version 7.10c to version 8.00: In Configure/Communication/Option, you can configure the “timeout before invalidating equipment variable”. Configuration in version 8.10 onwards: In Configure/Project/General Operation a window will appears in that open the folder Communication/Equipment, after you can configure the “timeout before invalidating equipment variable”. |
||
|
||
|
Created on: 30 Dec 2010 Last update: 13 May 2024