Topic
[KB146]Logging of Alarm Acknowledgements
Tags: Alarm, Scada Basic, Scripting
Options
Email
Print
| Applies to:
PcVue version 6.04d onwards. |
||
|
|
||
| Summary:
This article describes how to attribute alarm acknowledgement from SCADA Basic to the current user. |
||
|
|
||
| Details:
It is possible to acknowledge alarms from SCADA basic but, by default, the acknowledgement User Action is not logged.
Solution To enable the logging of alarm acknowledgement by SCADA Basic, as if it was done from an Alarm Viewer, use the following instruction. To enable logging: SYSTEM(“OPERATORMODE”,1); To disable logging: SYSTEM(“OPERATORMODE”,0); |
||
|
|
||
|