[KB243]The QUALITY field in OPC and the HDS

Tags: HDS, OPC, OPC-DA Client, PlantVue

14 years ago
By RM
Options
Print
Applies to:

PcVue all versions.


Summary:

This article refers to the format of the Quality field as defined in the specification of OPC Data Access 2.05a.


Details:

Please find the most common Quality field value you may find.

For more detail, the Quality field is defined in detail in the OPC specification. OPC Data Access Custom Interface Standard, Version 2.05A, 28th June 2002, paragraph 6.8 on pages 162-165.

To download it, visit the OPC Foundation web site. For downloading you have to create a useraccount and log in to the site.

Quality  Detail Status Value
Good Non specific 192
Good Local override 216
Uncertain Sub normal 88
Uncertain Unit Exceeded High 86
Uncertain Unit Exceeded Low 85
Uncertain Sensor not accurate 80
Uncertain Last Usable Value 68
Uncertain Non Specific 64
Bad Non Specific 0
Bad Configuration Error 4
Bad Not Connected 8
Bad Device Failure 12
Bad Sensor Failure 16
Bad Last known value 20
Bad Comm Failure 24
Bad Out of Service 28


Created on: 01 Dec 2010 Last update: 13 May 2024